Rear-Door Heat Exchanger Available Now

RDHX - Cabinet Enclosure

Integrated rear-door air-to-water cooling enclosure — 50–100 kW (water), plug-and-play, compatible with standard 19 in EIA-310-D server racks. Rear-door, swing-open access for quick rack service without disturbing IT hardware.

Best Suited For: High-Density Retrofit Enterprise Colocation

P/N: BSK-SCR-100  ·  Rev. 1.0 (2026)  ·  Warranty: Available on request

Rated Capacity50–100 kW (water)
Rack Compatibility19 in EIA-310-D, ≈48U
InstallationPlug-and-play, rear access
BITSINK RDHX - Cabinet Enclosure — rear-door air-to-water cooling unit, internal rack view, door open

Rear-door swing access

Rear-door, swing-open access for quick rack service and component swap without disturbing IT gear.

Plug-and-play install

Integrates directly with standard 19 in EIA-310-D racks — no facility rework required.

Variable-speed fan control

16 × 12 in axial fans modulate on outlet-air temperature to match real-time heat load.

Integrated leak detection

Leak/drip sensing built into the coil and plumbing, with continuous air and water temperature monitoring.

High-density capacity

50–100 kW of water-side cooling per rack, supporting high-density compute deployments.

Flexible fluid compatibility

Runs on water, oil, or glycol mixtures with a max working pressure of 10 bar (145 psi).

Overview
TypeIntegrated rear-door air-to-water cooling unit (fan-assisted)
Rated Cooling Capacity50–100 kW (water)
Cooling MethodAir-to-water heat exchange; rear-door drycooler coil
Cooling MediumWater or oil
Density ClassHigh-density rack cooling, up to 100 kW per rack
InstallationPlug-and-play; rear access for quick swap & maintenance
Dimensions & Construction
Overall L × W × H72.3 × 47.5 × 95.0 in (1.84 × 1.21 × 2.41 m)
Unit Weight (dry)950 lb (431 kg)
Operating Weight (filled)~992 lb (450 kg)
Coil Internal Volume5 US gal (19 L)
Housing MaterialSheet metal, painted / powder-coated exterior
AccessRear-door, swing-open for rack service
Compatible Server Rack
Designed for Rack Size36.1 × 24.0 × 90.0 in (L × W × H)
Rack Standard19 in equipment, EIA-310-D compatible
Rack Height Class≈ 48U
Rack Width24 in (600 mm), standard
CompatibilityAll standard server racks
Custom SizesAvailable upon request
Air-to-Water Cooler (Heat Exchanger)
Heat-Exchanger TypeFinned-tube air-to-water coil (rear-door)
Number of Coils1
Coil MaterialAluminum
Water Flow Rate (design)~60–120 L/min (16–32 GPM) for 50–100 kW
Water Inlet Temperature38 °C
Water Outlet Temperature50 °C
Water-Side Pressure Drop≈ 40 kPa (typical, at max flow)
Max Working Pressure≤ 10 bar (145 psi)
FluidWater or oil; glycol mixtures supported
Air Side & Fans
Number of Fans16 × 12 in (305 mm) axial
Airflow DirectionFront-to-back (rack exhaust through coil)
Air Flow (max)~12,000 CFM (20,400 m³/h)
Fan ControlVariable-speed on outlet-air temperature
Sound Level~75 dB(A) (typical)
Connection & Interface
Power Input (drycooler)380/480 V – 3 Phase, 50/60 Hz
Fluid Inlet / Outlet2 in aluminum adapter, NPL (2 total)
Feed OrientationTop or bottom
Working FluidWater or oil
Coil MaterialAluminum
Monitoring & Controls
Leak DetectionIntegrated leak / drip detection
SensingAir & water temperature, humidity, pressure
Fan ControlAutomatic speed control on outlet-air temperature
CommunicationsSNMP / Modbus / web UI (optional)
Fan RedundancyN+1 (optional)
Operating Environment
Ambient Temperature5 – 40 °C (indoor / data-center)
Relative Humidity20 – 80 % RH, non-condensing
Altitude≤ 1,000 m
Water RequirementSupply temperature above room dew point

Performance figures are design / typical values; actual capacity depends on water supply temperature, water flow rate, and rack airflow. Water temperature must remain above the room dew point unless dew-point control is provided. Monitoring, communications, and fan-redundancy items are typical / optional — confirm configuration with the factory.

The full technical data sheet (P/N BSK-SCR-100, Rev. 1.0) is available for immediate download above. Installation and CAD documentation are shared directly by our applications engineering team.

24/7 Field Service

Factory-trained technicians for deployed RDHX - Cabinet Enclosure units.

Warranty

Warranty terms available on request from applications engineering.

Spare Parts

Fans, coils, and leak sensors stocked regionally.

Contact Support

Retrofitting racks for rear-door cooling?

Our applications engineers will confirm rack compatibility and water loop sizing at no cost.