Product Available Now

1200A Industrial Control Panel

UL 508A listed enclosed industrial control panel, suitable for use as service equipment. 480Y/277 VAC, 65 kA SCCR, with a dedicated VFD branch and Class T/J fused outputs for pump and fan loads.

Best Suited For: Dry Cooler & Pump Control CDU / Mechanical Rooms

P/N: BS_UL_1200A_M1  ·  UL File: E529270  ·  Rev. 1.0 (2026)

Service Rating1,200 A
SCCR65 kA @ 480V
ListingUL 508A
BITSINK 1200A industrial control panel

UL 508A listed, service-equipment rated

Suitable for use as service equipment under UL File E529270.

Integrated VFD branch

20 HP AutomationDirect DURAPULSE sensorless vector VFD pre-wired into the panel.

Arc Reduction Maintenance System

Main breaker ARMS function lowers incident energy during live maintenance.

Active thermal management

Filtered forced-air cooling with adjustable thermostat, 40°C activation setpoint.

Dual-voltage control transformer

3,200 VA control transformer supports up to 5 UL 489 branch breakers.

Full documentation package

BOM, single-line, layout drawings, GFP test instructions, and FAT report included.

General Specifications
Panel TypeEnclosed Industrial Control Panel — Service Equipment
ListingUL 508A Listed — Suitable for Use as Service Equipment
UL FileE529270 (BITSINK LLC)
Supply Voltage480Y/277 VAC, 3-phase, 4-wire + ground, solidly grounded wye, 60 Hz
Service Rating1,200 A
Max Combined Continuous Load960 A
SCCR65 kA RMS symmetrical @ 480 VAC
Enclosure TypeUL / NEMA Type 1 — indoor, general purpose
Service Disconnect & Main OCPD
DeviceNoark M6N1200E3, 3-pole MCCB
Frame / Interrupting Rating1,200 A frame, 600 VAC max, 65 kA @ 480 VAC
Trip UnitLSIG (long-time/short-time/instantaneous/ground fault)
Arc ReductionIntegral Arc Reduction Maintenance System (ARMS)
Bus, Neutral & Grounding
Main Power Bus1/4 in × 5 in silver-plated copper, 3-phase
Neutral Disconnect Link1,250 A, installed for insulation testing
Main Bonding Jumper1/4 in × 5 in silver-plated copper, dedicated per NEC 250.28
Equipment Ground Bus1/4 in × 2 in copper, rated for 100 kA short-circuit withstand
480 VAC Branch Circuits
Branch Devices4 × Noark M2H250T3 (250A MCCB); 1 × 80A Class T fuse block (VFD branch); 1 × DURAPULSE GS23-4020 20HP VFD; 1 × 100A Class J fused output
Combined Continuous LoadLimited to 950 A
120 VAC Control Power
Control Transformer3,200 VA, single-phase, 480V primary, 115/230V dual-voltage
Secondary Protection15A Class CC fused; up to 5 UL 489 single-phase branch breakers
Active Thermal Management
System TypeActive forced-air, filtered intake/exhaust
Cooling Fans(4) × 39 CFM, 120 VAC, axial
ControlAdjustable thermostat, 0–60°C range, 40°C activation setpoint
Standards & Markings
Panel StandardUL 508A — Industrial Control Panels, Sections 73–79
Field MarkingAvailable fault current label per NEC 110.24; arc-flash label per NFPA 70E
DocumentationBOM, single-line, layout drawings, GFP test instructions, FAT report

Control panel submittals are issued directly by our electrical engineering team after a brief project qualification call.

24/7 Field Service

NETA-certified field engineers for commissioning, testing, and VFD support.

Warranty

Warranty terms available on request from applications engineering.

Spare Parts

VFDs, fuses, and branch breakers stocked regionally.

Contact Support

Pairing this with a dry cooler or CDU order?

Our electrical engineers will match the panel configuration to your pump and fan loads.