AiDC-2050 Chiller

2,050 kW air-to-water trim chiller engineered to work downstream of a dry cooler loop, holding facility leaving fluid temperature during peak-summer trim duty for expanded high-density GPU/ASIC rack deployments.

Best Suited For: Hyperscale AI Campuses Trim / Peak-Summer Cooling

Rev: Engineering Design Basis  ·  Warranty: Available on request

Nominal Cooling Capacity2,050 kW / 583 RT
Guaranteed Selection Target≥1,800 kW net @ 95°F
RefrigerantR-1234ze(E), A2L
AiDC-2050 Chiller — 2,050 kW air-to-water trim chiller

Eight independent circuits

8 independent refrigeration circuits at ~256 kW each for staged capacity and partial-load redundancy.

VSD compressors

8 × VSD semi-hermetic compressors modulate to match real-time trim load.

Dedicated plate heat exchangers

8 × dedicated refrigerant-to-glycol plate heat exchangers, one per circuit.

Low-GWP refrigerant

R-1234ze(E), a mildly-flammable (A2L) low-GWP refrigerant, reduces environmental impact versus legacy options.

Large-diameter EC fan array

16 large-diameter EC axial fans across 2 rows of 8 drive the V-bank microchannel condenser.

Dry-cooler economizer integration

Runs as second-stage trim behind a dry cooler economizer, engaging only when ambient exceeds the dry cooler's capability.

Engineering Design Basis
ApplicationTrim chiller downstream of dry cooler for expanded GB300 facility loop
Nominal Cooling Capacity2,050 kW / 583 RT
Required Peak-Summer Trim Duty~1,612 kW calculated
Guaranteed Selection Target≥ 1,800 kW net at 95°F ambient
Design Ambient95–104°F / 35°C
Entering Facility Fluid40.0°C / 104°F
Leaving Facility Fluid30.5°C / 86.9°F
Nominal Facility Flow700 GPM / 159 m³/h
Fluid70% DI water / 30% inhibited propylene glycol
Evaporator Pressure Drop Target≤ 15 psi / 103 kPa
Water-Side Working Pressure150 psig minimum
Mechanical
RefrigerantR-1234ze(E), A2L
Refrigeration Circuits8 independent circuits
Circuit Capacity~256 kW each
Compressor Architecture8 × VSD semi-hermetic compressors
Evaporator Architecture8 × dedicated refrigerant-to-glycol plate heat exchangers
Condenser ArchitectureV-bank microchannel air-cooled condenser
Fans16 × large-diameter EC axial fans; 2 rows × 8
Performance
Full-Load Chiller Input Target~460–550 kW at design point
Full-Load Heat Rejection Target~2,500–2,650 kW
Sound Target≤ 81 dBA at 10 ft (subject to final fan/coil selection)
Preliminary Performance Map
75°F / 24°C AmbientEWT 38°C · LWT 30.5°C · Net ~2,160 kW · Input ~400 kW · COP ~5.4
85°F / 29°C AmbientEWT 40°C · LWT 30.5°C · Net ~2,060 kW · Input ~440 kW · COP ~4.7
95°F / 35°C AmbientEWT 40°C · LWT 30.5°C · Net ~2,050 kW · Input ~500 kW · COP ~4.1
105°F / 41°C AmbientEWT 40°C · LWT 30.5°C · Net ~1,860 kW · Input ~550 kW · COP ~3.4
115°F / 46°C AmbientEWT 40°C · LWT 30.5°C · Net ~1,720 kW · Input ~610 kW · COP ~2.8
System Operating (Downstream of Dry Cooler)
Chiller to CDU~30.5°C / 86.9°F
Facility Return at Doubled Design Load~42°C / 107.6°F at ~700 GPM
Dry Cooler42°C entering → 40°C leaving
Dry Cooler Heat Rejection~340–350 kW at doubled flow/capacity basis
Residual Trim-Chiller Duty~1,610–1,620 kW
Chiller Leaving Target30.5°C maximum
Physical / Electrical
Overall DimensionsApprox. 480 × 96 × 96 in (12,192 × 2,438 × 2,438 mm)
Operating Weight Target~23,700 lb preliminary
Facility Connections8 in minimum; final by velocity / pressure-drop review
Electrical Service480 V / 3 phase / 60 Hz
Estimated MCA~860 A preliminary
Recommended MOCP1,000 A preliminary
ControlsPLC/HMI; BACnet/IP; Modbus TCP/RTU

Engineering design basis — preliminary technical data, subject to final engineering. Exact compressor model, refrigerant charge, MCA/MOCP, airflow, and PHE model require final OEM selection software at the stated duty point.

The full engineering design basis document is available for immediate download above. Installation and CAD documentation are shared directly by our applications engineering team.

24/7 Field Service

Factory-trained field engineers for deployed AiDC-2050 Chiller units.

Warranty

Warranty terms available on request from applications engineering.

Spare Parts

Compressors, PHEs, and EC fan modules stocked regionally.