Chiller Systems Available Now

AiDC-1050 Chiller

1,000 kW air-to-water trim chiller engineered to work downstream of a dry cooler loop, holding facility leaving fluid temperature during peak-summer trim duty for high-density GPU/ASIC rack deployments.

Best Suited For: Hyperscale AI Campuses Trim / Peak-Summer Cooling

Rev: Engineering Design Basis  ·  Warranty: Available on request

Nominal Cooling Capacity1,000 kW / 284 RT
Guaranteed Selection Target≥900 kW net @ 95°F
RefrigerantR-1234ze(E), A2L
AiDC-1050 Chiller — 1,000 kW air-to-water trim chiller

Four independent circuits

4 independent refrigeration circuits at ~250 kW each for staged capacity and partial-load redundancy.

VSD screw compressors

4 × VSD semi-hermetic screw compressors modulate to match real-time trim load.

Dedicated plate heat exchangers

4 × dedicated refrigerant-to-glycol plate heat exchangers, one per circuit.

Low-GWP refrigerant

R-1234ze(E), a mildly-flammable (A2L) low-GWP refrigerant, reduces environmental impact versus legacy options.

Large-diameter EC fan array

8 large-diameter EC axial fans across 2 rows of 4 drive the V-bank microchannel condenser.

Dry-cooler economizer integration

Runs as second-stage trim behind a dry cooler economizer, engaging only when ambient exceeds the dry cooler's capability.

Engineering Design Basis
ApplicationTrim chiller downstream of dry cooler for 7 × GB300 rack facility loop
Nominal Cooling Capacity1,000 kW / 284 RT
Required Peak-Summer Trim Duty~806 kW calculated
Guaranteed Selection Target≥ 900 kW net at 95°F ambient
Design Ambient95–104°F / 35°C
Entering Facility Fluid40.0°C / 104°F
Leaving Facility Fluid30.5°C / 86.9°F
Nominal Facility Flow350 GPM / 79.5 m³/h
Fluid70% DI water / 30% inhibited propylene glycol
Evaporator Pressure Drop Target≤ 15 psi / 103 kPa
Water-Side Working Pressure150 psig minimum
Mechanical
RefrigerantR-1234ze(E), A2L
Refrigeration Circuits4 independent circuits
Circuit Capacity~250 kW each
Compressor Architecture4 × VSD semi-hermetic screw compressors
Evaporator Architecture4 × dedicated refrigerant-to-glycol plate heat exchangers
Condenser ArchitectureV-bank microchannel air-cooled condenser
Fans8 × large-diameter EC axial fans; 2 rows × 4
Performance
Full-Load Chiller Input Target~230–275 kW at design point
Full-Load Heat Rejection Target~1,250–1,300 kW
Sound Target≤ 78 dBA at 10 ft (subject to final fan/coil selection)
Preliminary Performance Map
75°F / 24°C AmbientEWT 38°C · LWT 30.5°C · Net ~1,080 kW · Input ~200 kW · COP ~5.4
85°F / 29°C AmbientEWT 40°C · LWT 30.5°C · Net ~1,030 kW · Input ~220 kW · COP ~4.7
95°F / 35°C AmbientEWT 40°C · LWT 30.5°C · Net ~1,000 kW · Input ~245 kW · COP ~4.1
105°F / 41°C AmbientEWT 40°C · LWT 30.5°C · Net ~930 kW · Input ~275 kW · COP ~3.4
115°F / 46°C AmbientEWT 40°C · LWT 30.5°C · Net ~860 kW · Input ~305 kW · COP ~2.8
System Operating (Downstream of Dry Cooler)
Chiller to CDU~30.5°C / 86.9°F
CDU Return at ~980 kW Rack Load~42°C / 107.6°F at ~350 GPM
Dry Cooler42°C entering → 40°C leaving
Dry Cooler Heat Rejection~170–175 kW at stated condition
Residual Trim-Chiller Duty~805–810 kW
Chiller Leaving Target30.5°C maximum
Physical / Electrical
Overall Dimensions240 × 96 × 96 in (6,096 × 2,438 × 2,438 mm)
Operating Weight Target~11,850 lb
Facility Connections6 in minimum; final by velocity / pressure-drop review
Electrical Service480 V / 3 phase / 60 Hz
Estimated MCA~430 A preliminary
Recommended MOCP500 A preliminary
ControlsPLC/HMI; BACnet/IP; Modbus TCP/RTU

Engineering design basis — preliminary technical data, subject to final engineering. Exact compressor model, refrigerant charge, MCA/MOCP, airflow, and PHE model require final OEM selection software at the stated duty point.

The full engineering design basis document is available for immediate download above. Installation and CAD documentation are shared directly by our applications engineering team.

24/7 Field Service

Factory-trained field engineers for deployed AiDC-1050 Chiller units.

Warranty

Warranty terms available on request from applications engineering.

Spare Parts

Compressors, PHEs, and EC fan modules stocked regionally.

Contact Support

Sizing a trim chiller for a dry-cooler loop?

Share your rack heat load and dry cooler performance — we'll return a sizing proposal within 48 hours.